| Type | Load Break Switch RMU Vacuum Circuit Breaker RMU Fuse-Switch RMU Compact Integrated RMU | Model | FP-RMU-38 |
| Params | #### Common for Both Units Rated voltage 38kV; rated frequency 50/60Hz; rated current 600A; 1-minute power frequency withstand voltage 80kV; rated lightning impulse withstand voltage 150kV peak; rated short-circuit making current 52kA peak; rated short-time withstand current (main circuit) 25kA for 4s; rated peak withstand current 52kAp; electrical endurance capability class E2. Minimum SF₆ gas pressure at 20℃: 0.02MPa (relative); rated SF₆ gas pressure at 20℃: 0.04MPa (relative). Outer enclosure protection degree: IP4X, NEMA 1/2/3R; gas tank protection degree: IP67. #### Load Break Switch Unit Mechanical life: 5000 operations for load switch, 3000 operations for earthing switch. #### Breaker Unit Rated short-circuit breaking current 25kA; mechanical life: 10000 operations for VCB, 2000 operations for 3-position switch. | Material | - Stainless steel hermetically sealed gas tank - SF₆ insulated switching module - Spring energy storage operating mechanism - Cold-rolled steel outer cabinet with powder coating - Epoxy-cast cable entry bushings |
| Applicable Industry | Urban ring network distribution, residential complexes, commercial parks, street lighting systems, small industrial users, prefabricated substation integration | ||
- Compact fully sealed design for flexible installation in constrained spaces - Ring network architecture improves overall supply reliability - Maintenance-free design with low lifecycle operating cost - Multiple circuit configurations (incoming, outgoing, metering, tie) available - Suitable for both indoor and outdoor installation scenarios